Polycab HT Cables Technical Details

TABLE - 1 Conductor Technical Information for Single Core and Multicore cables conforming to IS-8I 30 Latest

(Stranded-Class-2) Copper & Aluminium Conductors

Nominal size of conductor
(sq.mm)
Minimum No. of Wires in the
conductor
Maximum D.C. Resistance
at 20° C
Maximum A.C. Resistance
at 90° C
Circular Compacted or
Shaped Conductor
Plain Copper
(ohm/Km)
Aluminium
(ohm/Km)
Plain Copper
(ohm/Km)
Aluminium
(ohm/Km)
Plain CopperAluminium
25 6 6 0.727 1.2 0.927 1.54
35 6 6 0.524 0.868 0.668 1.11
50 6 6 0.387 0.641 0.494 0.822
70 12 12 0.268 0.443 0.342 0.568
95 15 15 0.193 0.32 0.247 0.411
120 18 15 0.153 0.253 0.196 0.325
150 18 15 0.124 0.206 0.159 0.265
185 30 30 0.0991 0.164 0.128 0.211
240 34 30 0.0754 0.125 0.0982 0.161
300 34 30 0.0601 0.100 0.0792 0.130
400 53 53 0.047 0.0778 0.0632 0.102
500 53 53 0.0366 0.0605 0.0509 0.0801
630 53 53 0.0283 0.0469 0.0414 0.0634
800 53 53 0.0221 0.0367 0.0349 0.0513
1000 53 53 0.0176 0.0291 0.0306 0.0426

TABLE - 2 Short Circuit Rating for I Second Duration for Copper and Aluminium

XLPE Cables (Current In K. AMPS)

Short Circuit Current rating in KA/Sec
Nominal size of
conductor
(Sq. mm)
XLPE Insulated
CopperAluminium
25 3.58 2.35
35 5.01 3.29
50 7.15 4.70
70 10.01 6.58
95 13.59 8.93
120 17.16 11.28
150 21.45 14.10
185 26.46 17.39
240 34.32 22.56
300 42.90 28.20
400 57.20 37.60
500 71.50 47.00
630 90.09 59.22
800 114.40 75.20
1000 143.00 94.00

TABLE - 3 Capacitance

Approximate Capacitance (Microfarads/km) for Single Core Cables

Nominal size
(sq.mm)
Voltage Grade (KV)
3.8/6.66.6/6.6 &
6.35/11
11/1112.7/2219/3333/33
25 0.22 0.18 0.14
35 0.24 0.20 0.15 0.14
50 0.26 0.22 0.16 0.15 0.12
70 0.30 0.24 0.18 0.17 0.13
95 0.34 0.28 0.20 0.19 0.14 0.14
120 0.38 0.30 0.22 0.20 0.16 0.15
150 0.40 0.33 0.23 0.22 0.16 0.16
185 0.44 0.36 0.25 0.24 0.18 0.17
240 0.49 0.40 0.28 0.26 0.19 0.18
300 0.51 0.43 0.30 0.28 0.21 0.20
400 0.52 0.48 0.34 0.31 0.23 0.22
500 0.56 0.55 0.38 0.35 0.26 0.24
630 0.64 0.62 0.43 0.40 0.29 0.27
800 0.71 0.69 0.47 0.44 0.32 0.30
1000 0.75 0.75 0.51 0.47 0.34 0.32

TABLE - 4 Capacitance

Approximate Capacitance (Microfarads/km) for Multi Core Cables

Nominal size
(sq.mm)
Voltage Grade (KV)
3.8/6.66.6/6.6 &
6.35/11
11/1112.7/2219/3333/33
25 0.22 0.18 0.14
35 0.25 0.20 0.15 0.14
50 0.27 0.22 0.16 0.15 0.12
70 0.30 0.25 0.18 0.17 0.13
95 0.35 0.28 0.20 0.19 0.15 0.14
120 0.38 0.31 0.22 0.21 0.16 0.15
150 0.41 0.33 0.24 0.22 0.17 0.16
185 0.45 0.36 0.26 0.24 0.18 0.17
240 0.50 0.41 0.29 0.27 0.20 0.19
300 0.52 0.44 0.31 0.29 0.21 0.20
400 0.53 0.49 0.34 0.32 0.24 0.22

TABLE - 5 Reactance

Approximate Reactance At 50 Hz (Ohms/km) For Single Core Cables

SizeAluminium Flat Strip Armour
3.8/6.66.35/1111/1112.7/2219/3333/33
25 0.134 0.139 0.150
35 0.128 0.133 0.143 0.146
50 0.123 0.127 0.137 0.139 0.152
70 0.113 0.118 0.127 0.130 0.141
95 0.108 0.112 0.122 0.123 0.134 0.137
120 0.103 0.106 0.116 0.117 0.128 0.131
150 0.0999 0.104 0.112 0.114 0.125 0.127
185 0.0974 0.101 0.108 0.110 0.120 0.122
240 0.0936 0.0971 0.104 0.106 0.115 0.117
300 0.0914 0.0939 0.101 0.103 0.112 0.113
400 0.0892 0.0905 0.0971 0.0986 0.107 0.109
500 0.087 0.0873 0.0936 0.0949 0.102 0.104
630 0.0851 0.0858 0.0908 0.092 0.0996 0.101
800 0.0829 0.0833 0.0883 0.0895 0.0961 0.0977
1000 0.082 0.082 0.0867 0.088 0.0939 0.0955

SizeAluminium Round Wire Armour
3.8/6.66.35/1111/1112.7/2219/3333/33
25 0.139 0.144 0.154
35 0.132 0.137 0.147 0.149
50 0.127 0.131 0.142 0.144 0.156
70 0.117 0.122 0.131 0.134 0.145
95 0.112 0.116 0.125 0.128 0.139 0.141
120 0.106 0.111 0.120 0.122 0.132 0.134
150 0.104 0.108 0.117 0.118 0.128 0.130
185 0.101 0.106 0.112 0.114 0.123 0.126
240 0.0983 0.101 0.108 0.110 0.119 0.121
300 0.0958 0.098 0.105 0.106 0.116 0.118
400 0.0936 0.095 0.101 0.102 0.111 0.113
500 0.0905 0.091 0.097 0.0996 0.107 0.108
630 0.0886 0.089 0.096 0.0964 0.103 0.105
800 0.0877 0.088 0.092 0.0936 0.100 0.101
1000 0.0861 0.0861 0.0902 0.0917 0.0986 0.0999

SizeUnarmoured Cables
3.8/6.66.35/1111/1112.7/2219/3333/33
25 0.131 0.138 0.149
35 0.126 0.131 0.142 0.145
50 0.121 0.126 0.136 0.139 0.151
70 0.112 0.117 0.126 0.128 0.141
95 0.106 0.111 0.120 0.123 0.134 0.136
120 0.101 0.105 0.115 0.117 0.127 0.129
150 0.0986 0.102 0.112 0.113 0.123 0.126
185 0.0955 0.0999 0.107 0.109 0.119 0.122
240 0.093 0.0961 0.103 0.105 0.114 0.117
300 0.0908 0.093 0.0996 0.101 0.111 0.113
400 0.0886 0.0895 0.0964 0.098 0.106 0.108
500 0.0867 0.087 0.0924 0.0946 0.102 0.104
630 0.0845 0.0848 0.0905 0.0917 0.099 0.101
800 0.0826 0.0829 0.088 0.0892 0.0958 0.0974
1000 0.0817 0.0817 0.0861 0.088 0.0939 0.0955

TABLE - 6 Reactance

Approximate Reactance At 50 Hz (Ohms/km) For Multi Core Cables

SizeVoltage Grade (KV)
3.8/6.66.35/1111/1112.7/2219/3333/33
25 0.118 0.125 0.139
35 0.112 0.119 0.133 0.136
50 0.108 0.114 0.127 0.130 0.145
70 0.100 0.106 0.118 0.121 0.134
95 0.0958 0.101 0.112 0.114 0.127 0.130
120 0.0914 0.0964 0.106 0.109 0.121 0.124
150 0.0895 0.0939 0.104 0.106 0.117 0.120
185 0.087 0.0911 0.100 0.102 0.113 0.116
240 0.0842 0.088 0.0964 0.0983 0.109 0.111
300 0.0826 0.0855 0.0933 0.0952 0.105 0.107
400 0.0817 0.0829 0.0898 0.0917 0.101 0.103
500 0.0798 0.0801 0.0867 0.0883 0.0968 0.0986

TABLE 7 - 3.8 / 6.6 KV (E) HT XLPE Single Core Aluminium Conductor Cables

POLYCAB single core aluminium conductor, XLPE insulated, unarmoured & armoured cables conforming to IS: 7098 PART-2/ Latest

Nominal size
of conductor (sq.mm)
Nominal thickness of XLPE Insulation (mm)Unarmoured CablesMinimum Thickness
of inner Sheath
(mm)
Aluminium Flat Strip Armoured Cable
Nominal Thickness of PVC outer
sheath (mm)
Approx. Overall
diameter of
Cable (mm)
Approx. Weight
of Cable (kg/km)
Nominal Dimension
of Strip (mm)
Minimum Thickness
of PVC Outer
Sheath (mm)
Approx. Overall
diameter of
Cable (mm)
Approx. Weight
of cable (kg/km)
25 2.8 1.80 17 323 0.3 0.8 1.40 19 442
35 2.8 2.00 18 385 0.3 0.8 1.40 20 494
50 2.8 2.00 19 437 0.3 0.8 1.40 21 551
70 2.8 2.00 21 523 0.3 0.8 1.40 23 646
95 2.8 2.00 23 627 0.3 0.8 1.40 24 751
120 2.8 2.00 24 722 0.3 0.8 1.40 26 874
150 2.8 2.00 25 817 0.3 0.8 1.40 27 969
185 2.8 2.00 27 950 0.3 0.8 1.56 29 1131
240 2.8 2.20 30 1169 0.4 0.8 1.56 32 1349
300 3.0 2.20 32 1378 0.4 0.8 1.56 34 1587
400 3.3 2.20 36 1701 0.4 0.8 1.56 38 1919
500 3.5 2.40 39 2119 0.5 0.8 1.72 41 2385
630 3.5 2.40 43 2594 0.5 0.8 1.88 45 2917
800 3.5 2.60 48 3202 0.5 0.8 1.88 49 3496
1000 3.6 2.80 51 3886 0.6 0.8 2.04 53 4218

Nominal size
of conductor (sq.mm)
Aluminium Round Wire Armoured CableCurrent Carrying CapacityNormal Delivery
Length (Mtrs)
Nominal size of
armour (mm)
Minimum Thickness
of PVC Outer
Sheath (mm)
Approx. Overall
diameter of
Cable (mm)
Approx. Weight
of cable
(kg/km)
In Ground at
30°C (A)
In Air at
40°C (A)
In duct at
30°C (A)
25 1.60 1.40 21 513 99 115 88 500
35 1.60 1.40 22 580 117 139 104 500
50 1.60 1.40 23 637 138 166 123 500
70 1.60 1.40 24 732 168 208 149 500
95 1.60 1.40 26 855 200 252 177 500
120 1.60 1.40 28 969 227 292 201 500
150 1.60 1.56 29 1093 252 329 223 500
185 1.60 1.56 31 1245 285 380 251 500
240 2.00 1.56 34 1549 326 448 286 500
300 2.00 1.56 36 1796 365 511 319 500
400 2.00 1.72 39 2185 412 593 359 500
500 2.00 1.88 44 2670 461 680 401 500
630 2.00 1.88 48 3202 514 777 445 500
800 2.50 2.04 53 4000 552 863 476 500
1000 2.50 2.20 57 4760 595 954 509 500

TABLE 8 - 3.8 / 6.6 KV (E) HT XLPE Single Core Copper Conductor Cables

POLYCAB Single Core Copper Conductor, XLPE Insulated, Unarmoured & Armoured Cables Conforming to IS: 7098 PART-2/ Latest

Nominal size
of conductor (sq.mm)
Nominal thickness of XLPE Insulation (mm)Unarmoured CablesMinimum Thickness
of inner Sheath
(mm)
Aluminium Flat Strip Armoured Cable
Nominal Thickness of PVC outer
sheath (mm)
Approx. Overall
diameter of
Cable (mm)
Approx. Weight
of Cable (kg/km)
Nominal Dimension
of Strip (mm)
Minimum Thickness
of PVC Outer
Sheath (mm)
Approx. Overall
diameter of
Cable (mm)
Approx. Weight
of cable (kg/km)
25 2.8 1.80 17 466 0.3 0.8 1.40 19 589
35 2.8 2.00 18 580 0.3 0.8 1.40 20 694
50 2.8 2.00 20 713 0.3 0.8 1.40 21 827
70 2.8 2.00 21 912 0.3 0.8 1.40 23 1045
95 2.8 2.00 23 1159 0.3 0.8 1.40 24 1292
120 2.8 2.00 24 1397 0.3 0.8 1.40 26 1549
150 2.8 2.00 26 1653 0.3 0.8 1.40 27 1805
185 2.8 2.00 28 1995 0.3 0.8 1.56 29 2185
240 2.8 2.20 30 2546 0.4 0.8 1.56 32 2736
300 3.0 2.20 33 3116 0.4 0.8 1.56 34 3325
400 3.3 2.20 36 3924 0.4 0.8 1.56 38 4142
500 3.5 2.40 39 4950 0.5 0.8 1.72 41 5216
630 3.5 2.40 43 6261 0.5 0.8 1.88 45 6584
800 3.5 2.60 48 7895 0.5 0.8 1.88 49 8189
1000 3.6 2.80 52 9795 0.6 0.8 2.04 54 10137

Nominal size
of conductor (sq.mm)
Aluminium Round Wire Armoured CableCurrent Carrying CapacityNormal Delivery
Length (Mtrs)
Nominal size of
armour (mm)
Minimum Thickness
of PVC Outer
Sheath (mm)
Approx. Overall
diameter of
Cable (mm)
Approx. Weight
of cable
(kg/km)
In Ground at
30°C (A)
In Air at
40°C (A)
In duct at
30°C (A)
25 1.60 1.40 21 665 127 148 113 500
35 1.60 1.40 22 770 151 179 135 500
50 1.60 1.40 23 912 178 214 158 500
70 1.60 1.40 25 1131 216 267 192 500
95 1.60 1.40 26 1397 256 323 227 500
120 1.60 1.40 28 1644 290 374 257 500
150 1.60 1.56 29 1929 323 422 285 500
185 1.60 1.56 31 2299 362 484 319 500
240 2.00 1.56 34 2936 411 565 361 500
300 2.00 1.56 37 3534 456 641 400 500
400 2.00 1.72 40 4418 508 734 443 500
500 2.00 1.88 44 5501 559 828 486 500
630 2.00 1.88 48 6878 611 929 529 500
800 2.50 2.04 53 8683 638 1002 549 500
1000 2.50 2.20 58 10678 672 1083 575 500

TABLE 9 - 6.35/1 1 KV (E) & 6.6/6.6 KV (UE) HT XLPE Single Core Aluminium Conductor Cables

POLYCAB single core aluminium conductor, XLPE insulated, unarmoured & armoured cables conforming to IS: 7098 PART-2/Latest

Nominal size
of conductor (sq.mm)
Nominal thickness of XLPE Insulation (mm)Unarmoured CablesMinimum Thickness
of inner Sheath
(mm)
Aluminium Flat Strip Armoured Cable
Nominal Thickness of PVC outer
sheath (mm)
Approx. Overall
diameter of
Cable (mm)
Approx. Weight
of Cable (kg/km)
Nominal Dimension
of Strip (mm)
Minimum Thickness
of PVC Outer
Sheath (mm)
Approx. Overall
diameter of
Cable (mm)
Approx. Weight
of cable (kg/km)
25 3.6 2.00 19 385 0.3 0.8 1.40 21 504
35 3.6 2.00 20 437 0.3 0.8 1.40 22 561
50 3.6 2.00 21 494 0.3 0.8 1.40 23 608
70 3.6 2.00 23 580 0.3 0.8 1.40 24 713
95 3.6 2.00 24 684 0.3 0.8 1.40 26 836
120 3.6 2.00 26 789 0.3 0.8 1.40 28 941
150 3.6 2.00 27 884 0.3 0.8 1.56 29 1064
185 3.6 2.20 29 1045 0.4 0.8 1.56 31 1226
240 3.6 2.20 31 1245 0.4 0.8 1.56 33 1444
300 3.6 2.20 33 1444 0.4 0.8 1.56 35 1653
400 3.6 2.20 36 1729 0.4 0.8 1.72 38 1986
500 3.6 2.40 39 2138 0.5 0.8 1.72 41 2404
630 3.6 2.40 43 2613 0.5 0.8 1.88 46 2926
800 3.6 2.60 48 3221 0.5 0.8 1.88 50 3515
1000 3.6 2.80 51 3886 0.6 0.8 2.04 53 4218

Nominal size
of conductor (sq.mm)
Aluminium Round Wire Armoured CableCurrent Carrying CapacityNormal Delivery
Length (Mtrs)
Nominal size of
armour (mm)
Minimum Thickness
of PVC Outer
Sheath (mm)
Approx. Overall
diameter of
Cable (mm)
Approx. Weight
of cable
(kg/km)
In Ground at
30°C (A)
In Air at
40°C (A)
In duct at
30°C (A)
25 1.60 1.40 22 580 99 116 88 500
35 1.60 1.40 23 637 118 140 104 500
50 1.60 1.40 24 703 138 167 122 500
70 1.60 1.40 26 808 168 209 149 500
95 1.60 1.40 28 931 200 254 177 500
120 1.60 1.56 30 1074 227 294 200 500
150 1.60 1.56 31 1178 252 331 223 500
185 2.00 1.56 33 1416 284 383 250 500
240 2.00 1.56 36 1644 326 450 286 500
300 2.00 1.56 38 1872 365 512 319 500
400 2.00 1.72 40 2214 412 594 359 500
500 2.00 1.88 44 2689 461 680 401 500
630 2.00 1.88 48 3221 514 778 445 500
800 2.50 2.04 53 4009 553 863 476 500
1000 2.50 2.20 57 4760 595 954 509 500

TABLE 10 - 6.35/11  KV (E) & 6.6/6.6 KV (UE) HT XLPE Single Core Copper Conductor Cables

POLYCAB single core copper conductor, XLPE insulated, unarmoured & armoured cables conforming to IS: 7098 PART-2/Latest

Nominal size
of conductor (sq.mm)
Nominal thickness of XLPE Insulation (mm)Unarmoured CablesMinimum Thickness
of inner Sheath
(mm)
Aluminium Flat Strip Armoured Cable
Nominal Thickness of PVC outer
sheath (mm)
Approx. Overall
diameter of
Cable (mm)
Approx. Weight
of Cable (kg/km)
Nominal Dimension
of Strip (mm)
Minimum Thickness
of PVC Outer
Sheath (mm)
Approx. Overall
diameter of
Cable (mm)
Approx. Weight
of cable (kg/km)
25 3.6 2.00 19 532 0.3 0.8 1.40 21 646
35 3.6 2.00 20 637 0.3 0.8 1.40 22 751
50 3.6 2.00 21 760 0.3 0.8 1.40 23 893
70 3.6 2.00 23 969 0.3 0.8 1.40 25 1112
95 3.6 2.00 24 1226 0.3 0.8 1.40 26 1368
120 3.6 2.00 26 1463 0.3 0.8 1.40 28 1615
150 3.6 2.00 27 1720 0.3 0.8 1.56 29 1900
185 3.6 2.20 30 2100 0.4 0.8 1.56 31 2280
240 3.6 2.20 32 2622 0.4 0.8 1.56 34 2822
300 3.6 2.20 34 3183 0.4 0.8 1.56 36 3392
400 3.6 2.20 37 3952 0.4 0.8 1.72 39 4218
500 3.6 2.40 39 4969 0.5 0.8 1.72 41 5235
630 3.6 2.40 43 6280 0.5 0.8 1.88 46 6593
800 3.6 2.60 48 7914 0.5 0.8 1.88 50 8208
1000 3.6 2.80 52 9795 0.6 0.8 2.04 54 10137

Nominal size
of conductor (sq.mm)
Aluminium Round Wire Armoured CableCurrent Carrying CapacityNormal Delivery
Length (Mtrs)
Nominal size of
armour (mm)
Minimum Thickness
of PVC Outer
Sheath (mm)
Approx. Overall
diameter of
Cable (mm)
Approx. Weight
of cable
(kg/km)
In Ground at
30°C (A)
In Air at
40°C (A)
In duct at
30°C (A)
25 1.60 1.40 22 732 127 150 113 500
35 1.60 1.40 23 836 151 181 134 500
50 1.60 1.40 25 979 178 216 158 500
70 1.60 1.40 26 1207 216 269 191 500
95 1.60 1.40 28 1463 257 326 227 500
120 1.60 1.56 30 1748 290 376 256 500
150 1.60 1.56 31 2014 323 424 285 500
185 2.00 1.56 34 2480 360 487 317 500
240 2.00 1.56 36 3040 411 568 361 500
300 2.00 1.56 38 3610 456 643 399 500
400 2.00 1.72 41 4456 508 735 443 500
500 2.00 1.88 46 5529 559 828 486 500
630 2.00 1.88 48 6888 611 930 529 500
800 2.50 2.04 53 8702 639 1003 550 500
1000 2.50 2.20 58 10678 672 1083 575 500

TABLE 11 - 11/11 KV (UE) HT XLPE Single Core Aluminium Conductor Cables

POLYCAB Single Core Aluminium Conductor, XLPE Insulated, Unarmoured & Armoured Cables Conforming to IS: 7098 PART-2/Latest

Nominal size
of conductor (sq.mm)
Nominal thickness of XLPE Insulation (mm)Unarmoured CablesMinimum Thickness
of inner Sheath
(mm)
Aluminium Flat Strip Armoured Cable
Nominal Thickness of PVC outer
sheath (mm)
Approx. Overall
diameter of
Cable (mm)
Approx. Weight
of Cable (kg/km)
Nominal Dimension
of Strip (mm)
Minimum Thickness
of PVC Outer
Sheath (mm)
Approx. Overall
diameter of
Cable (mm)
Approx. Weight
of cable (kg/km)
25 5.5 2.00 23 523 0.3 0.8 1.40 25 656
35 5.5 2.00 24 570 0.3 0.8 1.40 26 713
50 5.5 2.00 25 637 0.3 0.8 1.40 27 779
70 5.5 2.00 26 732 0.3 0.8 1.56 28 903
95 5.5 2.00 28 846 0.3 0.8 1.56 30 1036
120 5.5 2.20 30 979 0.4 0.8 1.56 32 1169
150 5.5 2.20 31 1083 0.4 0.8 1.56 33 1283
185 5.5 2.20 33 1226 0.4 0.8 1.56 35 1435
240 5.5 2.20 35 1444 0.4 0.8 1.56 37 1663
300 5.5 2.20 37 1653 0.4 0.8 1.72 38 1910
400 5.5 2.40 39 1995 0.5 0.8 1.72 41 2261
500 5.5 2.40 43 2385 0.5 0.8 1.88 45 2698
630 5.5 2.60 48 2936 0.5 0.8 1.88 49 3230
800 5.5 2.80 52 3563 0.6 0.8 2.04 54 3895
1000 5.5 2.80 55 4199 0.6 0.8 2.20 57 4598

Nominal size
of conductor (sq.mm)
Aluminium Round Wire Armoured CableCurrent Carrying CapacityNormal Delivery
Length (Mtrs)
Nominal size of
armour (mm)
Minimum Thickness
of PVC Outer
Sheath (mm)
Approx. Overall
diameter of
Cable (mm)
Approx. Weight
of cable
(kg/km)
In Ground at
30°C (A)
In Air at
40°C (A)
In duct at
30°C (A)
25 1.60 1.40 26 751 99 116 88 500
35 1.60 1.40 27 808 118 140 104 500
50 1.60 1.56 29 903 138 167 122 500
70 1.60 1.56 30 1017 168 209 149 500
95 2.00 1.56 33 1216 200 254 177 500
120 2.00 1.56 34 1359 227 294 200 500
150 2.00 1.56 36 1482 252 331 223 500
185 2.00 1.56 37 1653 284 383 250 500
240 2.00 1.72 39 1919 326 450 286 500
300 2.00 1.72 41 2157 365 512 319 500
400 2.00 1.88 44 2556 412 594 359 500
500 2.50 2.04 49 3164 461 680 401 500
630 2.50 2.04 53 3724 514 778 445 500
800 2.50 2.20 58 4427 553 863 476 500
1000 2.50 2.36 61 5178 595 954 509 500

TABLE 12 - 11/11 KV (UE) HT XLPE Single Core Copper Conductor Cables

POLYCAB Single Core Copper Conductor, XLPE Insulated, Unarmoured & Armoured Cables Conforming to IS: 7098 PART-2/Latest

Nominal size
of conductor (sq.mm)
Nominal thickness of XLPE Insulation (mm)Unarmoured CablesMinimum Thickness
of inner Sheath
(mm)
Aluminium Flat Strip Armoured Cable
Nominal Thickness of PVC outer
sheath (mm)
Approx. Overall
diameter of
Cable (mm)
Approx. Weight
of Cable (kg/km)
Nominal Dimension
of Strip (mm)
Minimum Thickness
of PVC Outer
Sheath (mm)
Approx. Overall
diameter of
Cable (mm)
Approx. Weight
of cable (kg/km)
25 5.5 2.00 23 665 0.3 0.8 1.40 25 808
35 5.5 2.00 24 770 0.3 0.8 1.40 26 912
50 5.5 2.00 25 903 0.3 0.8 1.40 27 1055
70 5.5 2.00 27 1121 0.3 0.8 1.56 29 1302
95 5.5 2.00 28 1378 0.3 0.8 1.56 30 1568
120 5.5 2.20 30 1653 0.4 0.8 1.56 32 1843
150 5.5 2.20 31 1929 0.4 0.8 1.56 33 2119
185 5.5 2.20 33 2290 0.4 0.8 1.56 35 2489
240 5.5 2.20 36 2822 0.4 0.8 1.56 37 3050
300 5.5 2.20 38 3392 0.4 0.8 1.72 39 3648
400 5.5 2.40 40 4218 0.5 0.8 1.72 42 4484
500 5.5 2.40 43 5216 0.5 0.8 1.88 46 5529
630 5.5 2.60 48 6603 0.5 0.8 1.88 50 6897
800 5.5 2.80 52 8246 0.6 0.8 2.04 54 8579
1000 5.5 2.80 56 10108 0.6 0.8 2.20 58 10517

Nominal size
of conductor (sq.mm)
Aluminium Round Wire Armoured CableCurrent Carrying CapacityNormal Delivery
Length (Mtrs)
Nominal size of
armour (mm)
Minimum Thickness
of PVC Outer
Sheath (mm)
Approx. Overall
diameter of
Cable (mm)
Approx. Weight
of cable
(kg/km)
In Ground at
30°C (A)
In Air at
40°C (A)
In duct at
30°C (A)
25 1.60 1.40 26 893 127 150 113 500
35 1.60 1.40 27 1007 151 181 134 500
50 1.60 1.56 29 1178 178 216 158 500
70 1.60 1.56 30 1416 216 269 191 500
95 2.00 1.56 33 1758 257 326 227 500
120 2.00 1.56 34 2043 290 376 256 500
150 2.00 1.56 36 2328 323 424 285 500
185 2.00 1.56 38 2717 360 487 317 500
240 2.00 1.72 39 3316 411 568 361 500
300 2.00 1.72 41 3895 456 643 399 500
400 2.00 1.88 45 4788 508 735 443 500
500 2.50 2.04 49 5995 559 828 486 500
630 2.50 2.04 53 7391 611 930 529 500
800 2.50 2.20 58 9120 639 1003 550 500
1000 2.50 2.36 62 11087 672 1083 575 500

TABLE 13 - 12.7/22 KV (E) HT XLPE Single Core Aluminium Conductor Cables

POLYCAB Single Core Aluminium Conductor, XLPE Insulated, Unarmoured & Armoured Cables Conforming to IS: 7098 PART-2/Latest

Nominal size
of conductor (sq.mm)
Nominal thickness of XLPE Insulation (mm)Unarmoured CablesMinimum Thickness
of inner Sheath
(mm)
Aluminium Flat Strip Armoured Cable
Nominal Thickness of PVC outer
sheath (mm)
Approx. Overall
diameter of
Cable (mm)
Approx. Weight
of Cable (kg/km)
Nominal Dimension
of Strip (mm)
Minimum Thickness
of PVC Outer
Sheath (mm)
Approx. Overall
diameter of
Cable (mm)
Approx. Weight
of cable (kg/km)
35 6.0 2.00 25 608 0.3 0.8 1.40 27 760
50 6.0 2.00 26 675 0.3 0.8 1.56 28 855
70 6.0 2.00 27 770 0.3 0.8 1.56 29 960
95 6.0 2.20 29 912 0.4 0.8 1.56 31 1102
120 6.0 2.20 31 1026 0.4 0.8 1.56 33 1226
150 6.0 2.20 32 1131 0.4 0.8 1.56 34 1340
185 6.0 2.20 34 1283 0.4 0.8 1.56 36 1501
240 6.0 2.20 36 1501 0.4 0.8 1.56 38 1720
300 6.0 2.20 38 1710 0.4 0.8 1.72 39 1976
400 6.0 2.40 40 2052 0.5 0.8 1.88 43 2356
500 6.0 2.60 45 2499 0.5 0.8 1.88 46 2774
630 6.0 2.60 49 3012 0.5 0.8 2.04 51 3344
800 6.0 2.80 53 3639 0.6 0.8 2.04 55 3981
1000 6.0 3.00 56 4332 0.6 0.8 2.20 58 4693

Nominal size
of conductor (sq.mm)
Aluminium Round Wire Armoured CableCurrent Carrying CapacityNormal Delivery
Length (Mtrs)
Nominal size of
armour (mm)
Minimum Thickness
of PVC Outer
Sheath (mm)
Approx. Overall
diameter of
Cable (mm)
Approx. Weight
of cable
(kg/km)
In Ground at
30°C (A)
In Air at
40°C (A)
In duct at
30°C (A)
35 1.60 1.56 29 884 116 144 102 500
50 1.60 1.56 30 960 137 174 120 500
70 1.60 1.56 31 1064 167 217 146 500
95 2.00 1.56 34 1292 198 262 172 500
120 2.00 1.56 35 1425 224 302 195 500
150 2.00 1.56 37 1549 249 339 217 500
185 2.00 1.72 38 1739 280 389 243 500
240 2.00 1.72 40 1986 321 455 278 500
300 2.00 1.72 42 2223 355 515 307 500
400 2.00 1.88 45 2622 400 594 345 500
500 2.50 2.04 50 3249 447 678 384 500
630 2.50 2.04 54 3819 496 770 424 500
800 2.50 2.20 59 4522 543 866 475 500
1000 2.50 2.36 62 5282 572 944 498 500

TABLE 14 - 12.7 / 22 KV (E) HT XLPE Single Core Copper Conductor Cables

POLYCAB Single Core Copper Conductor, XLPE Insulated, Unarmoured & Armoured Cables Conforming to IS: 7098 PART-2/Latest

Nominal size
of conductor (sq.mm)
Nominal thickness of XLPE Insulation (mm)Unarmoured CablesMinimum Thickness
of inner Sheath
(mm)
Aluminium Flat Strip Armoured Cable
Nominal Thickness of PVC outer
sheath (mm)
Approx. Overall
diameter of
Cable (mm)
Approx. Weight
of Cable (kg/km)
Nominal Dimension
of Strip (mm)
Minimum Thickness
of PVC Outer
Sheath (mm)
Approx. Overall
diameter of
Cable (mm)
Approx. Weight
of cable (kg/km)
35 6.0 2.00 25 808 0.3 0.8 1.40 27 960
50 6.0 2.00 26 950 0.3 0.8 1.56 28 1121
70 6.0 2.00 28 1169 0.3 0.8 1.56 30 1359
95 6.0 2.20 29 1454 0.4 0.8 1.56 31 1634
120 6.0 2.20 31 1701 0.4 0.8 1.56 33 1900
150 6.0 2.20 32 1976 0.4 0.8 1.56 34 2176
185 6.0 2.20 34 2337 0.4 0.8 1.56 36 2556
240 6.0 2.20 37 2879 0.4 0.8 1.56 38 3107
300 6.0 2.20 39 3449 0.4 0.8 1.72 40 3724
400 6.0 2.40 41 4285 0.5 0.8 1.88 44 4589
500 6.0 2.60 45 5330 0.5 0.8 1.88 47 5615
630 6.0 2.60 49 6679 0.5 0.8 2.04 51 7021
800 6.0 2.80 53 8332 0.6 0.8 2.04 55 8674
1000 6.0 3.00 57 10251 0.6 0.8 2.20 59 10612

Nominal size
of conductor (sq.mm)
Aluminium Round Wire Armoured CableCurrent Carrying CapacityNormal Delivery
Length (Mtrs)
Nominal size of
armour (mm)
Minimum Thickness
of PVC Outer
Sheath (mm)
Approx. Overall
diameter of
Cable (mm)
Approx. Weight
of cable
(kg/km)
In Ground at
30°C (A)
In Air at
40°C (A)
In duct at
30°C (A)
35 1.60 1.56 29 1083 150 185 132 500
50 1.60 1.56 30 1235 176 224 154 500
70 1.60 1.56 31 1473 214 278 187 500
95 2.00 1.56 34 1834 253 336 221 500
120 2.00 1.56 35 2109 285 386 249 500
150 2.00 1.56 37 2385 317 434 276 500
185 2.00 1.72 38 2803 355 494 308 500
240 2.00 1.72 40 3382 404 575 350 500
300 2.00 1.72 42 3962 442 644 382 500
400 2.00 1.88 46 4864 490 734 422 500
500 2.50 2.04 50 6080 538 825 462 500
630 2.50 2.04 54 7486 586 920 501 500
800 2.50 2.20 59 9215 629 1014 550 500
1000 2.50 2.36 63 11201 643 1074 560 500

TABLE 15 - 19 / 33 KV (E) HT XLPE Single Core Aluminium Conductor Cables

POLYCAB Single Core Aluminium Conductor, XLPE Insulated, Unarmoured & Armoured Cables Conforming to IS: 7098 PART-2/Latest

Nominal size
of conductor (sq.mm)
Nominal thickness of XLPE Insulation (mm)Unarmoured CablesMinimum Thickness
of inner Sheath
(mm)
Aluminium Flat Strip Armoured Cable
Nominal Thickness of PVC outer
sheath (mm)
Approx. Overall
diameter of
Cable (mm)
Approx. Weight
of Cable (kg/km)
Nominal Dimension
of Strip (mm)
Minimum Thickness
of PVC Outer
Sheath (mm)
Approx. Overall
diameter of
Cable (mm)
Approx. Weight
of cable (kg/km)
70 8.8 2.20 33 1064 0.4 0.8 1.56 35 1273
95 8.8 2.20 35 1197 0.4 0.8 1.56 37 1416
120 8.8 2.20 37 1321 0.4 0.8 1.72 39 1577
150 8.8 2.20 38 1444 0.4 0.8 1.72 40 1701
185 8.8 2.40 39 1634 0.5 0.8 1.72 41 1891
240 8.8 2.40 41 1872 0.5 0.8 1.72 44 2185
300 8.8 2.60 44 2147 0.5 0.8 1.72 45 2423
400 8.8 2.60 47 2489 0.5 0.8 1.72 49 2812
500 8.8 2.80 51 2955 0.6 0.8 1.72 52 3287
630 8.8 2.80 55 3506 0.6 0.8 1.72 57 3895
800 8.8 3.00 59 4171 0.6 0.8 1.72 61 4589
1000 8.8 3.20 62 4902 0.7 0.8 1.72 64 5311

Nominal size
of conductor (sq.mm)
Aluminium Round Wire Armoured CableCurrent Carrying CapacityNormal Delivery
Length (Mtrs)
Nominal size of
armour (mm)
Minimum Thickness
of PVC Outer
Sheath (mm)
Approx. Overall
diameter of
Cable (mm)
Approx. Weight
of cable
(kg/km)
In Ground at
30°C (A)
In Air at
40°C (A)
In duct at
30°C (A)
70 2.00 1.56 38 1492 167 217 146 500
95 2.00 1.72 39 1672 198 262 172 500
120 2.00 1.72 40 1824 224 302 195 500
150 2.00 1.72 41 1957 249 339 217 500
185 2.00 1.88 44 2185 280 389 243 500
240 2.00 1.88 46 2451 321 455 278 500
300 2.50 2.04 49 2879 355 515 307 500
400 2.50 2.04 52 3268 400 594 345 500
500 2.50 2.20 56 3819 447 678 384 500
630 2.50 2.36 61 4465 496 770 424 500
800 2.50 2.36 65 5149 543 866 475 500
1000 3.15 2.52 69 6204 572 944 498 500

TABLE 16 - 19 / 33 KV (E) HT XLPE Single Core Copper Conductor Cables

POLYCAB Single Core Copper Conductor, XLPE Insulated, Unarmoured & Armoured Cables Conforming to IS: 7098 PART-2/Latest

Nominal size
of conductor (sq.mm)
Nominal thickness of XLPE Insulation (mm)Unarmoured CablesMinimum Thickness
of inner Sheath
(mm)
Aluminium Flat Strip Armoured Cable
Nominal Thickness of PVC outer
sheath (mm)
Approx. Overall
diameter of
Cable (mm)
Approx. Weight
of Cable (kg/km)
Nominal Dimension
of Strip (mm)
Minimum Thickness
of PVC Outer
Sheath (mm)
Approx. Overall
diameter of
Cable (mm)
Approx. Weight
of cable (kg/km)
70 8.8 2.20 34 1463 0.4 0.8 1.56 36 1672
95 8.8 2.20 35 1739 0.4 0.8 1.56 37 1948
120 8.8 2.20 37 2005 0.4 0.8 1.72 39 2252
150 8.8 2.20 38 2280 0.4 0.8 1.72 40 2546
185 8.8 2.40 40 2698 0.5 0.8 1.72 41 2964
240 8.8 2.40 42 3259 0.5 0.8 1.88 44 3563
300 8.8 2.60 44 3895 0.5 0.8 1.88 46 4161
400 8.8 2.60 47 4722 0.5 0.8 2.04 49 5054
500 8.8 2.80 51 5795 0.6 0.8 2.04 53 6128
630 8.8 2.80 55 7173 0.6 0.8 2.20 57 7562
800 8.8 3.00 59 8864 0.6 0.8 2.36 61 9282
1000 8.8 3.20 63 10821 0.7 0.8 2.36 65 11239

Nominal size
of conductor (sq.mm)
Aluminium Round Wire Armoured CableCurrent Carrying CapacityNormal Delivery
Length (Mtrs)
Nominal size of
armour (mm)
Minimum Thickness
of PVC Outer
Sheath (mm)
Approx. Overall
diameter of
Cable (mm)
Approx. Weight
of cable
(kg/km)
In Ground at
30°C (A)
In Air at
40°C (A)
In duct at
30°C (A)
70 2.00 1.56 38 1891 214 278 187 500
95 2.00 1.72 39 2214 253 336 221 500
120 2.00 1.72 40 2499 285 386 249 500
150 2.00 1.72 42 2793 317 434 276 500
185 2.00 1.88 44 3259 355 494 308 500
240 2.00 1.88 46 3838 404 575 350 500
300 2.50 2.04 50 4627 442 644 382 500
400 2.50 2.04 53 5510 490 734 422 500
500 2.50 2.20 56 6650 538 825 462 500
630 2.50 2.36 61 8132 586 920 501 500
800 2.50 2.36 65 9833 629 1014 550 500
1000 3.15 2.52 70 12151 643 1074 560 500

TABLE 17 - 33/33 KV (UE) HT XLPE Single Core Aluminium Conductor Cable

POLYCAB Single Core Aluminium Conductor, XLPE Insulated, Unarmoured & Armoured Cables Conforming to IS: 7098 PART-2/Latest

Nominal size
of conductor (sq.mm)
Nominal thickness of XLPE Insulation (mm)Unarmoured CablesMinimum Thickness
of inner Sheath
(mm)
Aluminium Flat Strip Armoured Cable
Nominal Thickness of PVC outer
sheath (mm)
Approx. Overall
diameter of
Cable (mm)
Approx. Weight
of Cable (kg/km)
Nominal Dimension
of Strip (mm)
Minimum Thickness
of PVC Outer
Sheath (mm)
Approx. Overall
diameter of
Cable (mm)
Approx. Weight
of cable (kg/km)
95 9.5 2.20 36 1273 0.4 0.8 1.72 39 1530
120 9.5 2.20 38 1406 0.4 0.8 1.72 40 1672
150 9.5 2.40 39 1558 0.5 0.8 1.72 41 1815
185 9.5 2.40 40 1729 0.5 0.8 1.72 42 1995
240 9.5 2.40 43 1967 0.5 0.8 1.88 45 2280
300 9.5 2.60 45 2252 0.5 0.8 1.88 47 2527
400 9.5 2.60 48 2594 0.5 0.8 2.04 50 2926
500 9.5 2.80 52 3069 0.6 0.8 2.04 54 3401
630 9.5 3.00 56 3677 0.6 0.8 2.20 58 4028
800 9.5 3.00 60 4304 0.6 0.8 2.36 63 4731
1000 9.5 3.20 64 5035 0.7 0.8 2.52 66 5510

Nominal size
of conductor (sq.mm)
Aluminium Round Wire Armoured CableCurrent Carrying CapacityNormal Delivery
Length (Mtrs)
Nominal size of
armour (mm)
Minimum Thickness
of PVC Outer
Sheath (mm)
Approx. Overall
diameter of
Cable (mm)
Approx. Weight
of cable
(kg/km)
In Ground at
30°C (A)
In Air at
40°C (A)
In duct at
30°C (A)
95 2.00 1.72 40 1777 198 262 172 500
120 2.00 1.72 42 1919 224 302 195 500
150 2.00 1.88 43 2109 249 339 217 500
185 2.00 1.88 45 2299 280 389 243 500
240 2.50 2.04 49 2736 321 455 278 500
300 2.50 2.04 51 2993 355 515 307 500
400 2.50 2.20 54 3420 400 594 345 500
500 2.50 2.20 58 3943 447 678 384 500
630 2.50 2.36 62 4598 496 770 424 500
800 3.15 2.52 68 5586 543 866 475 500
1000 3.15 2.68 71 6422 572 944 498 500

TABLE 18 - 33/33 KV (UE) HT XLPE Single Core Copper Conductor Cable

POLYCAB Single Core Copper Conductor, XLPE Insulated, Unarmoured & Armoured Cables Conforming to IS: 7098 PART-2/Latest

Nominal size
of conductor (sq.mm)
Nominal thickness of XLPE Insulation (mm)Unarmoured CablesMinimum Thickness
of inner Sheath
(mm)
Aluminium Flat Strip Armoured Cable
Nominal Thickness of PVC outer
sheath (mm)
Approx. Overall
diameter of
Cable (mm)
Approx. Weight
of Cable (kg/km)
Nominal Dimension
of Strip (mm)
Minimum Thickness
of PVC Outer
Sheath (mm)
Approx. Overall
diameter of
Cable (mm)
Approx. Weight
of cable (kg/km)
95 9.5 2.20 36 1815 0.4 0.8 1.72 39 2062
120 9.5 2.20 38 2081 0.4 0.8 1.72 40 2347
150 9.5 2.40 40 2404 0.5 0.8 1.72 41 2660
185 9.5 2.40 41 2784 0.5 0.8 1.72 43 3059
240 9.5 2.40 43 3354 0.5 0.8 1.88 45 3667
300 9.5 2.60 45 3990 0.5 0.8 1.88 47 4275
400 9.5 2.60 49 4826 0.5 0.8 2.04 51 5168
500 9.5 2.80 52 5909 0.6 0.8 2.04 54 6251
630 9.5 3.00 57 7344 0.6 0.8 2.20 58 7695
800 9.5 3.00 60 8997 0.6 0.8 2.36 63 9424
1000 9.5 3.20 65 10963 0.7 0.8 2.52 67 11429

Nominal size
of conductor (sq.mm)
Aluminium Round Wire Armoured CableCurrent Carrying CapacityNormal Delivery
Length (Mtrs)
Nominal size of
armour (mm)
Minimum Thickness
of PVC Outer
Sheath (mm)
Approx. Overall
diameter of
Cable (mm)
Approx. Weight
of cable
(kg/km)
In Ground at
30°C (A)
In Air at
40°C (A)
In duct at
30°C (A)
95 2.00 1.72 40 2309 253 336 221 500
120 2.00 1.72 42 2594 285 386 249 500
150 2.00 1.88 43 2945 317 434 276 500
185 2.00 1.88 45 3354 355 494 308 500
240 2.50 2.04 49 4133 404 575 350 500
300 2.50 2.04 51 4750 442 644 382 500
400 2.50 2.20 55 5672 490 734 422 250
500 2.50 2.20 58 6783 538 825 462 250
630 2.50 2.36 62 8284 586 920 501 250
800 3.15 2.52 68 10279 629 1014 550 250
1000 3.15 2.68 72 12360 643 1074 560 250

TABLE 19 - 3.8/6.6 KV (E) HT XLPE Three Core Aluminium Conductor Cables

POLYCAB Three Core Aluminium Conductor, XLPE Insulated, Unarmoured & Armoured Cables Conforming to IS: 7098 PART-2/Latest

Nominal size
of conductor (sq.mm)
Nominal thickness of XLPE Insulation (mm)Unarmoured CablesMinimum Thickness
of inner Sheath
(mm)
Galvanised Steel Flat Strip Armoured Cable
Nominal Thickness of PVC outer
sheath (mm)
Approx. Overall
diameter of
Cable (mm)
Approx. Weight
of Cable (kg/km)
Nominal Dimension
of Strip (mm)
Minimum Thickness
of PVC Outer
Sheath (mm)
Approx. Overall
diameter of
Cable (mm)
Approx. Weight
of cable (kg/km)
25 2.8 2.20 34 1227 0.4 0.8 1.56 36 1672
35 2.8 2.20 37 1401 0.4 0.8 1.72 38 1891
50 2.8 2.40 39 1653 0.5 0.8 1.72 40 2157
70 2.8 2.40 42 1969 0.5 0.8 1.88 43 2537
95 2.8 2.60 46 2409 0.5 0.8 1.88 47 2964
120 2.8 2.80 50 2860 0.6 0.8 2.04 51 3449
150 2.8 2.80 52 3219 0.6 0.8 2.20 54 3886
185 2.8 3.00 57 3770 0.6 0.8 2.20 57 4427
240 2.8 3.20 62 4603 0.7 0.8 2.36 63 5330
300 3.0 3.40 68 5493 0.7 0.8 2.52 68 6251
400 3.3 3.80 76 6888 0.7 0.8 2.84 76 7705
500 Please Contact our Technical & Design department for more information
630 Please Contact our Technical & Design department for more information

Nominal size
of conductor (sq.mm)
Galvanised Steel Round Wire Armoured CableCurrent Carrying CapacityNormal Delivery
Length (Mtrs)
Nominal size of
armour (mm)
Minimum Thickness
of PVC Outer
Sheath (mm)
Approx. Overall
diameter of
Cable (mm)
Approx. Weight
of cable
(kg/km)
In Ground at
30°C (A)
In Air at
40°C (A)
In duct at
30°C (A)
25 2.00 1.72 38 2252 94 102 81 500
35 2.00 1.72 40 2489 112 123 96 500
50 2.00 1.88 42 2812 131 146 113 500
70 2.00 1.88 45 3221 160 182 138 500
95 2.50 2.04 50 4133 191 221 165 500
120 2.50 2.20 54 4722 216 254 187 500
150 2.50 2.20 57 5187 241 286 208 500
185 2.50 2.36 61 5881 273 330 236 500
240 3.15 2.52 68 7543 315 385 277 500
300 3.15 2.68 73 8645 354 440 312 500
400 4.00 3.00 82 11419 403 512 355 500
500 Please Contact our Technical & Design department for more information
630 Please Contact our Technical & Design department for more information

TABLE 20 - 3.8/6.6 KV (E) HT XLPE Three Core Copper Conductor Cables

POLYCAB Three Core Copper Conductor, XLPE Insulated, Unarmoured & Armoured Cables Conforming to IS: 7098 PART-2/Latest

Nominal size
of conductor (sq.mm)
Nominal thickness of XLPE Insulation (mm)Unarmoured CablesMinimum Thickness
of inner Sheath
(mm)
Galvanised Steel Flat Strip Armoured Cable
Nominal Thickness of PVC outer
sheath (mm)
Approx. Overall
diameter of
Cable (mm)
Approx. Weight
of Cable (kg/km)
Nominal Dimension
of Strip (mm)
Minimum Thickness
of PVC Outer
Sheath (mm)
Approx. Overall
diameter of
Cable (mm)
Approx. Weight
of cable (kg/km)
25 2.8 2.20 35 1666 0.4 0.8 1.56 36 2109
35 2.8 2.20 37 1994 0.4 0.8 1.72 38 2480
50 2.8 2.40 40 2477 0.5 0.8 1.72 40 2974
70 2.8 2.40 43 3167 0.5 0.8 1.88 44 3734
95 2.8 2.60 46 4019 0.5 0.8 1.88 47 4579
120 2.8 2.80 50 4890 0.6 0.8 2.04 51 5482
150 2.8 2.80 53 5734 0.6 0.8 2.20 54 6403
185 2.8 3.00 58 6957 0.6 0.8 2.20 58 7638
240 2.8 3.20 63 8765 0.7 0.8 2.36 63 9491
300 3.0 3.40 69 10733 0.7 0.8 2.52 69 11505
400 3.3 3.80 78 13630 0.7 0.8 2.84 78 14469
500 Please Contact our Technical & Design department for more information
630 Please Contact our Technical & Design department for more information

Nominal size
of conductor (sq.mm)
Galvanised Steel Round Wire Armoured CableCurrent Carrying CapacityNormal Delivery
Length (Mtrs)
Nominal size of
armour (mm)
Minimum Thickness
of PVC Outer
Sheath (mm)
Approx. Overall
diameter of
Cable (mm)
Approx. Weight
of cable
(kg/km)
In Ground at
30°C (A)
In Air at
40°C (A)
In duct at
30°C (A)
25 2.00 1.72 39 2708 121 132 104 500
35 2.00 1.72 40 3088 144 159 124 500
50 2.00 1.88 43 3658 169 188 146 500
70 2.00 1.88 46 4446 206 234 178 500
95 2.50 2.04 50 5738 246 284 212 500
120 2.50 2.20 54 6755 278 326 240 500
150 2.50 2.20 57 7705 310 368 268 500
185 2.50 2.36 62 9063 350 422 302 500
240 3.15 2.52 68 11704 401 492 353 500
300 3.15 2.68 74 13880 449 559 395 250
400 4.00 3.00 84 18259 506 642 445 200
500 Please Contact our Technical & Design department for more information
630 Please Contact our Technical & Design department for more information

TABLE 21 - 6.35/11 KV (E) & 6.6/6.6 KV (UE) HT XLPE Three Core Aluminium Conductor Cables

POLYCAB Three Core Aluminium Conductor, XLPE Insulated, Unarmoured & Armoured Cables Conforming to IS: 7098 PART-2/Latest

Nominal size
of conductor (sq.mm)
Nominal thickness of XLPE Insulation (mm)Unarmoured CablesMinimum Thickness
of inner Sheath
(mm)
Galvanised Steel Flat Strip Armoured Cable
Nominal Thickness of PVC outer
sheath (mm)
Approx. Overall
diameter of
Cable (mm)
Approx. Weight
of Cable (kg/km)
Nominal Dimension
of Strip (mm)
Minimum Thickness
of PVC Outer
Sheath (mm)
Approx. Overall
diameter of
Cable (mm)
Approx. Weight
of cable (kg/km)
25 3.6 2.20 38 1436 0.4 0.8 1.72 39 1948
35 3.6 2.40 40 1676 0.5 0.8 1.72 41 2176
50 3.6 2.60 43 1938 0.5 0.8 1.88 43 2461
70 3.6 2.60 46 2273 0.5 0.8 1.88 47 2831
95 3.6 2.80 50 2751 0.6 0.8 2.04 51 3344
120 3.6 2.80 54 3155 0.6 0.8 2.20 54 3848
150 3.6 3.00 57 3578 0.6 0.8 2.20 57 4237
185 3.6 3.20 61 4184 0.7 0.8 2.36 61 4893
240 3.6 3.40 67 5037 0.7 0.8 2.52 67 5776
300 3.6 3.60 71 5846 0.7 0.8 2.68 71 6622
400 3.6 3.80 78 7042 0.7 0.8 2.84 78 7876
500 Please Contact our Technical & Design department for more information
630 Please Contact our Technical & Design department for more information

Nominal size
of conductor (sq.mm)
Galvanised Steel Round Wire Armoured CableCurrent Carrying CapacityNormal Delivery
Length (Mtrs)
Nominal size of
armour (mm)
Minimum Thickness
of PVC Outer
Sheath (mm)
Approx. Overall
diameter of
Cable (mm)
Approx. Weight
of cable
(kg/km)
In Ground at
30°C (A)
In Air at
40°C (A)
In duct at
30°C (A)
25 2.00 1.72 41 2575 94 103 81 500
35 2.00 1.88 44 2879 112 124 97 500
50 2.50 2.04 47 3553 131 148 114 500
70 2.50 2.04 50 4000 161 184 139 500
95 2.50 2.20 54 4617 190 222 165 500
120 2.50 2.20 58 5168 216 256 188 500
150 2.50 2.36 61 5653 242 288 209 500
185 3.15 2.52 66 7011 273 330 240 500
240 3.15 2.68 72 8066 315 387 278 500
300 3.15 2.84 76 9101 354 441 312 250
400 4.00 3.00 83 11571 404 512 356 250
500 Please Contact our Technical & Design department for more information
630 Please Contact our Technical & Design department for more information

TABLE 22 - 6.35 / I I KV (E) & 6.6 / 6.6 KV (UE) HT XLPE Three Core Copper Conductor Cables

POLYCAB Three Core Copper Conductor, XLPE Insulated, Unarmoured & Armoured Cables Conforming to IS: 7098 PART-2/Latest

Nominal size
of conductor (sq.mm)
Nominal thickness of XLPE Insulation (mm)Unarmoured CablesMinimum Thickness
of inner Sheath
(mm)
Galvanised Steel Flat Strip Armoured Cable
Nominal Thickness of PVC outer
sheath (mm)
Approx. Overall
diameter of
Cable (mm)
Approx. Weight
of Cable (kg/km)
Nominal Dimension
of Strip (mm)
Minimum Thickness
of PVC Outer
Sheath (mm)
Approx. Overall
diameter of
Cable (mm)
Approx. Weight
of cable (kg/km)
25 3.6 2.20 39 1871 0.4 0.8 1.72 39 2385
35 3.6 2.40 40 2269 0.5 0.8 1.72 41 2765
50 3.6 2.60 43 2763 0.5 0.8 1.88 44 3287
70 3.6 2.60 47 3469 0.5 0.8 1.88 47 4028
95 3.6 2.80 50 4362 0.6 0.8 2.04 51 4950
120 3.6 2.80 54 5184 0.6 0.8 2.20 54 5871
150 3.6 3.00 57 6094 0.6 0.8 2.20 57 6755
185 3.6 3.20 62 7375 0.7 0.8 2.36 62 8075
240 3.6 3.40 67 9194 0.7 0.8 2.52 67 9928
300 3.6 3.60 72 11091 0.7 0.8 2.68 72 11866
400 3.6 3.80 78 13787 0.7 0.8 2.84 78 14640
500 Please Contact our Technical & Design department for more information
630 Please Contact our Technical & Design department for more information

Nominal size
of conductor (sq.mm)
Galvanised Steel Round Wire Armoured CableCurrent Carrying CapacityNormal Delivery
Length (Mtrs)
Nominal size of
armour (mm)
Minimum Thickness
of PVC Outer
Sheath (mm)
Approx. Overall
diameter of
Cable (mm)
Approx. Weight
of cable
(kg/km)
In Ground at
30°C (A)
In Air at
40°C (A)
In duct at
30°C (A)
25 2.00 1.72 41 3012 121 133 105 500
35 2.00 1.88 44 3477 144 160 125 500
50 2.50 2.04 47 4380 169 191 146 500
70 2.50 2.04 51 5225 207 237 179 500
95 2.50 2.20 54 6223 245 286 213 500
120 2.50 2.20 58 7192 278 329 241 500
150 2.50 2.36 61 8208 311 371 269 500
185 3.15 2.52 67 10260 349 422 308 500
240 3.15 2.68 72 12284 401 493 354 250
300 3.15 2.84 77 14402 449 560 396 250
400 4.00 3.00 85 18506 506 643 446 250
500 Please Contact our Technical & Design department for more information
630 Please Contact our Technical & Design department for more information

TABLE 23 - 11/11 KV (UE) HT XLPE Three Core Aluminium Conductor Cables

POLYCAB Three Core Aluminium Conductor, XLPE Insulated, Unarmoured & Armoured Cables Conforming to IS: 7098 PART-2/Latest

Nominal size
of conductor (sq.mm)
Nominal thickness of XLPE Insulation (mm)Unarmoured CablesMinimum Thickness
of inner Sheath
(mm)
Galvanised Steel Flat Strip Armoured Cable
Nominal Thickness of PVC outer
sheath (mm)
Approx. Overall
diameter of
Cable (mm)
Approx. Weight
of Cable (kg/km)
Nominal Dimension
of Strip (mm)
Minimum Thickness
of PVC Outer
Sheath (mm)
Approx. Overall
diameter of
Cable (mm)
Approx. Weight
of cable (kg/km)
25 5.5 2.60 47 2110 0.5 0.8 1.88 47 2670
35 5.5 2.80 49 2369 0.5 0.8 2.04 50 2964
50 5.5 2.80 52 2636 0.6 0.8 2.20 52 3287
70 5.5 3.00 55 3062 0.6 0.8 2.20 56 3705
95 5.5 3.20 59 3576 0.6 0.8 2.36 60 4266
120 5.5 3.20 63 4056 0.7 0.8 2.36 63 4779
150 5.5 3.40 66 4539 0.7 0.8 2.52 66 5273
185 5.5 3.40 70 5111 0.7 0.8 2.68 70 5938
240 5.5 3.60 75 6020 0.7 0.8 2.84 75 6888
300 5.5 3.80 79 6888 0.7 0.8 3.00 79 7800
400 5.5 4.00 85 8170 0.7 0.8 3.00 85 9082
500 Please Contact our Technical & Design department for more information
630 Please Contact our Technical & Design department for more information

Nominal size
of conductor (sq.mm)
Galvanised Steel Round Wire Armoured CableCurrent Carrying CapacityNormal Delivery
Length (Mtrs)
Nominal size of
armour (mm)
Minimum Thickness
of PVC Outer
Sheath (mm)
Approx. Overall
diameter of
Cable (mm)
Approx. Weight
of cable
(kg/km)
In Ground at
30°C (A)
In Air at
40°C (A)
In duct at
30°C (A)
25 2.50 2.04 51 3867 94 103 81 500
35 2.50 2.20 53 4199 112 124 97 500
50 2.50 2.20 56 4532 131 148 114 500
70 2.50 2.36 59 5102 161 184 139 500
95 3.15 2.52 65 6346 190 222 165 500
120 3.15 2.52 68 7002 216 256 188 500
150 3.15 2.68 71 7572 242 288 209 500
185 3.15 2.84 75 8370 273 330 240 500
240 3.15 3.00 79 9500 315 387 278 250
300 4.00 3.00 85 11609 354 441 312 250
400 4.00 3.00 91 13177 404 512 356 250
500 Please Contact our Technical & Design department for more information
630 Please Contact our Technical & Design department for more information

TABLE 24 - 11/11 KV (UE) HT XLPE Three Core Copper Conductor Cables

Three Core Copper Conductor, XLPE Insulated, Unarmoured & Armoured Cables Conforming to IS: 7098 PART-2/Latest

Nominal size
of conductor (sq.mm)
Nominal thickness of XLPE Insulation (mm)Unarmoured CablesMinimum Thickness
of inner Sheath
(mm)
Galvanised Steel Flat Strip Armoured Cable
Nominal Thickness of PVC outer
sheath (mm)
Approx. Overall
diameter of
Cable (mm)
Approx. Weight
of Cable (kg/km)
Nominal Dimension
of Strip (mm)
Minimum Thickness
of PVC Outer
Sheath (mm)
Approx. Overall
diameter of
Cable (mm)
Approx. Weight
of cable (kg/km)
25 5.5 2.60 47 2553 0.5 0.8 1.88 47 3107
35 5.5 2.80 49 2961 0.5 0.8 2.04 50 3553
50 5.5 2.80 52 3466 0.6 0.8 2.20 53 4133
70 5.5 3.00 56 4274 0.6 0.8 2.20 56 4931
95 5.5 3.20 59 5186 0.6 0.8 2.36 60 5871
120 5.5 3.20 63 6085 0.7 0.8 2.36 63 6812
150 5.5 3.40 66 7057 0.7 0.8 2.52 66 7790
185 5.5 3.40 71 8314 0.7 0.8 2.68 71 9158
240 5.5 3.60 76 10195 0.7 0.8 2.84 75 11087
300 5.5 3.80 79 12143 0.7 0.8 3.00 80 13072
400 5.5 4.00 87 14937 0.7 0.8 3.00 87 15865
500 Please Contact our Technical & Design department for more information
630 Please Contact our Technical & Design department for more information

Nominal size
of conductor (sq.mm)
Galvanised Steel Round Wire Armoured CableCurrent Carrying CapacityNormal Delivery
Length (Mtrs)
Nominal size of
armour (mm)
Minimum Thickness
of PVC Outer
Sheath (mm)
Approx. Overall
diameter of
Cable (mm)
Approx. Weight
of cable
(kg/km)
In Ground at
30°C (A)
In Air at
40°C (A)
In duct at
30°C (A)
25 2.50 2.04 51 4313 121 133 105 500
35 2.50 2.20 53 4788 144 160 125 500
50 2.50 2.20 56 5406 169 191 146 500
70 2.50 2.36 60 6308 207 237 179 500
95 3.15 2.52 65 7961 245 286 213 500
120 3.15 2.52 68 9025 278 329 241 500
150 3.15 2.68 71 10089 311 371 269 500
185 3.15 2.84 76 11628 349 422 308 250
240 3.15 3.00 80 13737 401 493 354 250
300 4.00 3.00 86 16863 449 560 396 250
400 4.00 3.00 93 20036 506 643 446 250
500 Please Contact our Technical & Design department for more information
630 Please Contact our Technical & Design department for more information

TABLE 25 - 12.7/22 KV (E) HT XLPE Three Core Aluminium Conductor Cables

Three Core Aluminium Conductor, XLPE Insulated, Unarmoured & Armoured Cables Conforming to IS: 7098 PART-2/Latest

Nominal size
of conductor (sq.mm)
Nominal thickness of XLPE Insulation (mm)Unarmoured CablesMinimum Thickness
of inner Sheath
(mm)
Galvanised Steel Flat Strip Armoured Cable
Nominal Thickness of PVC outer
sheath (mm)
Approx. Overall
diameter of
Cable (mm)
Approx. Weight
of Cable (kg/km)
Nominal Dimension
of Strip (mm)
Minimum Thickness
of PVC Outer
Sheath (mm)
Approx. Overall
diameter of
Cable (mm)
Approx. Weight
of cable (kg/km)
35 6.0 2.80 52 2575 0.6 0.8 2.04 52 3183
50 6.0 3.00 54 2868 0.6 0.8 2.20 54 3506
70 6.0 3.00 57 3265 0.6 0.8 2.36 58 3990
95 6.0 3.20 62 3820 0.7 0.8 2.36 62 4522
120 6.0 3.40 66 4359 0.7 0.8 2.52 66 5102
150 6.0 3.40 68 4769 0.7 0.8 2.68 69 5577
185 6.0 3.60 72 5427 0.7 0.8 2.68 72 6223
240 6.0 3.80 78 6349 0.7 0.8 2.84 78 7182
300 6.0 4.00 81 7246 0.7 0.8 3.00 81 8104
400 6.0 4.00 87 8474 0.7 0.8 3.00 87 9424
500 Please Contact our Technical & Design department for more information
630 Please Contact our Technical & Design department for more information

Nominal size
of conductor (sq.mm)
Galvanised Steel Round Wire Armoured CableCurrent Carrying CapacityNormal Delivery
Length (Mtrs)
Nominal size of
armour (mm)
Minimum Thickness
of PVC Outer
Sheath (mm)
Approx. Overall
diameter of
Cable (mm)
Approx. Weight
of cable
(kg/km)
In Ground at
30°C (A)
In Air at
40°C (A)
In duct at
30°C (A)
35 2.50 2.20 56 4475 111 127 97 500
50 2.50 2.36 58 4874 130 152 116 500
70 2.50 2.36 61 5377 159 189 142 500
95 3.15 2.52 67 6707 189 227 169 500
120 3.15 2.68 71 7391 215 262 192 500
150 3.15 2.68 73 7914 239 294 214 250
185 3.15 2.84 77 8740 270 336 245 250
240 4.00 3.00 83 10878 312 393 282 250
300 4.00 3.00 87 11980 351 448 317 250
400 4.00 3.00 94 13566 400 519 361 250
500 Please Contact our Technical & Design department for more information
630 Please Contact our Technical & Design department for more information

TABLE 26 - 12.7/22 KV (E) HT XLPE Three Core Copper Conductor Cables

Three Core Copper Conductor, XLPE Insulated, Unarmoured & Armoured Cables Conforming to IS: 7098 PART-2/Latest

Nominal size
of conductor (sq.mm)
Nominal thickness of XLPE Insulation (mm)Unarmoured CablesMinimum Thickness
of inner Sheath
(mm)
Galvanised Steel Flat Strip Armoured Cable
Nominal Thickness of PVC outer
sheath (mm)
Approx. Overall
diameter of
Cable (mm)
Approx. Weight
of Cable (kg/km)
Nominal Dimension
of Strip (mm)
Minimum Thickness
of PVC Outer
Sheath (mm)
Approx. Overall
diameter of
Cable (mm)
Approx. Weight
of cable (kg/km)
35 6.0 2.80 52 3168 0.6 0.8 2.04 52 3781
50 6.0 3.00 55 3708 0.6 0.8 2.20 55 4351
70 6.0 3.00 58 4463 0.6 0.8 2.36 59 5187
95 6.0 3.20 62 5431 0.7 0.8 2.36 62 6137
120 6.0 3.40 66 6388 0.7 0.8 2.52 66 7125
150 6.0 3.40 68 7297 0.7 0.8 2.68 69 8104
185 6.0 3.60 73 8624 0.7 0.8 2.68 73 9415
240 6.0 3.80 78 10525 0.7 0.8 2.84 78 11362
300 6.0 4.00 82 12504 0.7 0.8 3.00 82 13376
400 6.0 4.00 89 15234 0.7 0.8 3.00 89 16198
500 Please Contact our Technical & Design department for more information
630 Please Contact our Technical & Design department for more information
Nominal size
of conductor (sq.mm)
Galvanised Steel Round Wire Armoured CableCurrent Carrying CapacityNormal Delivery
Length (Mtrs)
Nominal size of
armour (mm)
Minimum Thickness
of PVC Outer
Sheath (mm)
Approx. Overall
diameter of
Cable (mm)
Approx. Weight
of cable
(kg/km)
In Ground at
30°C (A)
In Air at
40°C (A)
In duct at
30°C (A)
35 2.50 2.20 56 5064 143 164 125 500
50 2.50 2.36 59 5710 167 196 150 500
70 2.50 2.36 62 6612 204 243 183 500
95 3.15 2.52 67 8313 243 293 217 500
120 3.15 2.68 71 9424 276 336 246 500
150 3.15 2.68 74 10441 307 378 275 250
185 3.15 2.84 78 11989 346 431 313 250
240 4.00 3.00 84 15153 398 503 360 250
300 4.00 3.00 88 17328 446 571 403 250
400 4.00 3.00 95 20416 503 655 453 250
500 Please Contact our Technical & Design department for more information
630 Please Contact our Technical & Design department for more information

TABLE 27 - 19/33 KV (E) HT XLPE Three Core Aluminium Conductor Cables

Three Core Aluminium Conductor, XLPE Insulated, Unarmoured & Armoured Cables Conforming to IS: 7098 PART-2/Latest

Nominal size
of conductor (sq.mm)
Nominal thickness of XLPE Insulation (mm)Unarmoured CablesMinimum Thickness
of inner Sheath
(mm)
Galvanised Steel Flat Strip Armoured Cable
Nominal Thickness of PVC outer
sheath (mm)
Approx. Overall
diameter of
Cable (mm)
Approx. Overall
diameter of
Cable (mm)
Approx. Weight
of Cable (kg/km)
Nominal Dimension
of Strip (mm)
Minimum Thickness
of PVC Outer
Sheath (mm)
Approx. Overall
diameter of
Cable (mm)
Approx. Overall
diameter of
Cable (mm)
Approx. Weight
of cable (kg/km)
70 8.8 3.60 73 71 4723 0.7 0.8 2.68 73 71 5501
95 8.8 3.60 77 75 5269 0.7 0.8 2.84 77 75 6137
120 8.8 3.80 81 78 5870 0.7 0.8 2.84 80 78 6707
150 8.8 4.00 84 81 6412 0.7 0.8 3.00 83 80 7268
185 8.8 4.00 87 84 7069 0.7 0.8 3.00 87 84 7961
240 8.8 4.00 92 89 8012 0.7 0.8 3.00 92 89 8978
300 8.8 4.00 96 93 8908 0.7 0.8 3.00 96 93 9899
400 8.8 4.00 103 100 10245 0.7 0.8 3.00 102 99 11305
500 Please Contact our Technical & Design department for more information
630 Please Contact our Technical & Design department for more information

Nominal size
of conductor (sq.mm)
Galvanised Steel Round Wire Armoured CableCurrent Carrying CapacityNormal Delivery
Length (Mtrs)
Nominal size of
armour (mm)
Minimum Thickness
of PVC Outer
Sheath (mm)
Approx. Overall
diameter of
Cable (mm)
Approx. Overall
diameter of
Cable (mm)
Approx. Weight
of cable
(kg/km)
In Ground at
30°C (A)
In Air at
40°C (A)
In duct at
30°C (A)
70 3.15 2.84 78 76 7980 159 189 142 500
95 3.15 3.00 82 79 8750 189 227 169 500
120 4.00 3.00 87 84 10498 215 262 192 500
150 4.00 3.00 90 87 11144 239 294 214 250
185 4.00 3.00 93 90 11980 270 336 245 250
240 4.00 3.00 98 95 13196 312 393 282 250
300 4.00 3.00 102 99 14374 351 448 317 250
400 4.00 3.00 109 106 16065 400 519 361 250
500 Please Contact our Technical & Design department for more information
630 Please Contact our Technical & Design department for more information

TABLE 28 - 19 / 33 KV (E) HT XLPE Three Core Copper Conductor Cables

Three Core Copper Conductor, XLPE Insulated, Unarmoured & Armoured Cables Conforming to IS: 7098 PART-2/Latest

Nominal size
of conductor (sq.mm)
Nominal thickness of XLPE Insulation (mm)Unarmoured CablesMinimum Thickness
of inner Sheath
(mm)
Galvanised Steel Flat Strip Armoured Cable
Nominal Thickness of PVC outer
sheath (mm)
Approx. Overall
diameter of
Cable (mm)
Approx. Overall
diameter of
Cable (mm)
Approx. Weight
of Cable (kg/km)
Nominal Dimension
of Strip (mm)
Minimum Thickness
of PVC Outer
Sheath (mm)
Approx. Overall
diameter of
Cable (mm)
Approx. Overall
diameter of
Cable (mm)
Approx. Weight
of cable (kg/km)
70 8.8 3.60 74 72 5943 0.7 0.8 2.68 74 72 6717
95 8.8 3.60 77 75 6879 0.7 0.8 2.84 77 75 7743
120 8.8 3.80 81 78 7899 0.7 0.8 2.84 80 78 8731
150 8.8 4.00 84 81 8934 0.7 0.8 3.00 84 81 9795
185 8.8 4.00 88 85 10291 0.7 0.8 3.00 88 85 11201
240 8.8 4.00 93 90 12213 0.7 0.8 3.00 93 90 13177
300 8.8 4.00 97 94 14182 0.7 0.8 3.00 97 94 15200
400 8.8 4.00 104 101 17047 0.7 0.8 3.00 104 101 18155
500 Please Contact our Technical & Design department for more information
630 Please Contact our Technical & Design department for more information

Nominal size
of conductor (sq.mm)
Galvanised Steel Round Wire Armoured CableCurrent Carrying CapacityNormal Delivery
Length (Mtrs)
Nominal size of
armour (mm)
Minimum Thickness
of PVC Outer
Sheath (mm)
Approx. Overall
diameter of
Cable (mm)
Approx. Overall
diameter of
Cable (mm)
Approx. Weight
of cable
(kg/km)
In Ground at
30°C (A)
In Air at
40°C (A)
In duct at
30°C (A)
70 3.15 2.84 79 77 9196 204 243 183 250
95 3.15 3.00 82 79 10365 243 293 217 250
120 4.00 3.00 87 84 12521 276 336 246 250
150 4.00 3.00 90 87 13671 307 378 275 250
185 4.00 3.00 94 91 15305 346 431 313 250
240 4.00 3.00 99 96 17490 398 503 360 250
300 4.00 3.00 103 100 19741 446 571 403 200
400 4.00 3.00 110 107 22962 503 655 453 200
500 Please Contact our Technical & Design department for more information
630 Please Contact our Technical & Design department for more information

TABLE 29 - 33/33 KV (UE) HT XLPE Three Core Aluminium Conductor Cables

Three Core Aluminium Conductor, XLPE Insulated, Unarmoured & Armoured Cables Conforming to IS: 7098 PART-2/Latest

Nominal size
of conductor (sq.mm)
Nominal thickness of XLPE Insulation (mm)Unarmoured CablesMinimum Thickness
of inner Sheath
(mm)
Galvanised Steel Flat Strip Armoured Cable
Nominal Thickness of PVC outer
sheath (mm)
Approx. Overall
diameter of
Cable (mm)
Approx. Overall
diameter of
Cable (mm)
Approx. Weight
of Cable (kg/km)
Nominal Dimension
of Strip (mm)
Minimum Thickness
of PVC Outer
Sheath (mm)
Approx. Overall
diameter of
Cable (mm)
Approx. Overall
diameter of
Cable (mm)
Approx. Weight
of cable (kg/km)
95 9.5 3.80 80 77 5713 0.7 0.8 2.84 80 77 6546
120 9.5 4.00 84 81 6325 0.7 0.8 3.00 84 81 7182
150 9.5 4.00 87 84 6806 0.7 0.8 3.00 86 83 7695
185 9.5 4.00 90 87 7478 0.7 0.8 3.00 90 87 8398
240 9.5 4.00 95 92 8456 0.7 0.8 3.00 95 92 9453
300 9.5 4.00 99 96 9358 0.7 0.8 3.00 99 96 10384
400 9.5 4.00 106 103 10719 0.7 0.8 3.00 105 102 11818
500 Please Contact our Technical & Design department for more information
630 Please Contact our Technical & Design department for more information

Nominal size
of conductor (sq.mm)
Galvanised Steel Round Wire Armoured CableCurrent Carrying CapacityNormal Delivery
Length (Mtrs)
Nominal size of
armour (mm)
Minimum Thickness
of PVC Outer
Sheath (mm)
Approx. Overall
diameter of
Cable (mm)
Approx. Overall
diameter of
Cable (mm)
Approx. Weight
of cable
(kg/km)
In Ground at
30°C (A)
In Air at
40°C (A)
In duct at
30°C (A)
95 4.00 3.00 87 84 10336 189 227 169 500
120 4.00 3.00 90 87 11058 215 262 192 250
150 4.00 3.00 93 90 11723 239 294 214 250
185 4.00 3.00 96 93 12578 270 336 245 250
240 4.00 3.00 101 98 13823 312 393 282 250
300 4.00 3.00 106 103 15001 351 448 317 250
400 4.00 3.00 112 109 16730 400 519 361 250
500 Please Contact our Technical & Design department for more information
630 Please Contact our Technical & Design department for more information

TABLE 30 - 33/33 KV (UE) HT XLPE Three Core Copper Conductor Cables

Three Core Aluminium Conductor, XLPE Insulated, Unarmoured & Armoured Cables Conforming to IS: 7098 PART-2/ Latest

Nominal size
of conductor (sq.mm)
Nominal thickness of XLPE Insulation (mm)Unarmoured CablesMinimum Thickness
of inner Sheath
(mm)
Galvanised Steel Flat Strip Armoured Cable
Nominal Thickness of PVC outer
sheath (mm)
Approx. Overall
diameter of
Cable (mm)
Approx. Overall
diameter of
Cable (mm)
Approx. Weight
of Cable (kg/km)
Nominal Dimension
of Strip (mm)
Minimum Thickness
of PVC Outer
Sheath (mm)
Approx. Overall
diameter of
Cable (mm)
Approx. Overall
diameter of
Cable (mm)
Approx. Weight
of cable (kg/km)
95 9.5 3.80 80 77 7323 0.7 0.8 2.84 80 77 8161
120 9.5 4.00 84 81 8354 0.7 0.8 3.00 84 81 9206
150 9.5 4.00 87 84 9330 0.7 0.8 3.00 87 84 10222
185 9.5 4.00 91 88 10705 0.7 0.8 3.00 91 88 11647
240 9.5 4.00 96 93 12646 0.7 0.8 3.00 96 93 13642
300 9.5 4.00 100 97 14634 0.7 0.8 3.00 100 97 15685
400 9.5 4.00 107 104 17529 0.7 0.8 3.00 107 104 18649
500 Please Contact our Technical & Design department for more information
630 Please Contact our Technical & Design department for more information

Nominal size
of conductor (sq.mm)
Galvanised Steel Round Wire Armoured CableCurrent Carrying CapacityNormal Delivery
Length (Mtrs)
Nominal size of
armour (mm)
Minimum Thickness
of PVC Outer
Sheath (mm)
Approx. Overall
diameter of
Cable (mm)
Approx. Overall
diameter of
Cable (mm)
Approx. Weight
of cable
(kg/km)
In Ground at
30°C (A)
In Air at
40°C (A)
In duct at
30°C (A)
95 4.00 3.00 87 84 11951 243 293 217 250
120 4.00 3.00 90 87 13091 276 336 246 250
150 4.00 3.00 93 90 14250 307 378 275 250
185 4.00 3.00 97 94 15894 346 431 313 250
240 4.00 3.00 102 99 18107 398 503 360 250
300 4.00 3.00 106 103 20368 446 571 403 200
400 4.00 3.00 114 111 23627 503 655 453 200
500 Please Contact our Technical & Design department for more information
630 Please Contact our Technical & Design department for more information