Schneider Contactors Technical Details

TeSys D Green Contactors

For Motor Control up to 37 kW / 400 V Category AC-3

3 Pole Contactors
Standard power ratings of 3-phase motors
50-60 Hz in category AC-3
(Ɵ ≤ 60 °C)
Rated
Operational
Current  in AC-3  440 V
up to
Instantaneous
Auxiliary
Contact
Basic reference,
to be completed by adding  the control voltage code
Weight
220 V
230 V
380 V
400 V
415 V440 V500 V660 V
690 V
 
kWkWkWkWkWkWA  FixingKg
Connection by Screw Clamp Terminals
2.2 4 4 4 5.5 5.5 9 1 1 LC1D09●●● 0.368
3 5.5 5.5 5.5 7.5 7.5 12 1 1 LC1D12●●● 0.373
4 7.5 9 9 10 10 18 1 1 LC1D18●●● 0.378
5.5 11 11 11 15 15 25 1 1 LC1D25●●● 0.433
7.5 15 15 15 18.5 18.5 32 1 1 LC1D32●●● 0.438
9 18.5 18.5 18.5 18.5 18.5 38 1 1 LC1D38●●● 0.442
Power Connections by EverLink BTR  Screw Connectors and Control by Screw Clamp Terminal
11 18.5 22 22 22 30 40 1 1 LC1D40A●●● 0.992
15 22 25 30 30 33 55 1 1 LC1D50A●●● 0.997
18.5 30 37 37 37 37 65 1 1 LC1D65A●●● 1.002
22 37 37 37 45 45 80 1 1 LC1D80A●●● 1.002
Control Voltage Codes
AC/DC Supply
Volts 24 (DC Only) 24-60 48-130 100-250 250 V - 415 V AC/
250 V - 500 V DC
LC1D09 ...D38,
LC1D40A ... D80A
U 0.85...1.1 Uc BNE EHE KUE USE
LC1D40A ... D80
U 0.8...1.2 Uc BBE  

TeSys D Green Reversing Contactors

For Motor Control up to 37 kW / 400 V Category AC-3

3-Pole Reversing Contactors
Standard power ratings of 3-phase motors
50-60 Hz in category AC-3
(Ɵ ≤ 60 °C)
Rated
Operational
Current  in AC-3  440 V
up to
Instantaneous
Auxiliary
Contact per
Contactor
Contactors supplied with coil Partial reference, to be completed by adding the control voltage codeWeight
220 V
230 V
380 V
400 V
415 V440 V500 V660 V
690 V
   
kWkWkWkWkWkWA  FixingKg
With Mechanical Interlock, without Electrical Interlocking, for Connection by Screw Clamp Terminals or Everlink BTR Screw Connectors 
2.2 4 4 4 5.5 5.5 9 1 1 LC2D09●●● 0.783
3 5.5 5.5 5.5 7.5 7.5 12 1 1 LC2D12●●● 0.793
4 7.5 9 9 10 10 18 1 1 LC2D18●●● 0.803
5.5 11 11 11 15 15 25 1 1 LC2D25●●● 0.913
7.5 15 15 15 18.5 18.5 32 1 1 LC2D32●●● 0.923
9 18.5 18.5 18.5 18.5 18.5 38 1 1 LC2D38●●● 0.933
11 18.5 22 22 22 30 40 1 1 LC2D40A●●● 2.154
15 22 25 30 30 33 50 1 1 LC2D50A●●● 2.164
18.5 30 37 37 37 37 65 1 1 LC2D65A●●● 2.174
22 37 37 37 45 45 80 1 1 LC2D80A●●● 2.174
Coil Voltage Codes
AC/DC Supply
Volts 24 (DC only) 24-60 48-130 100-250 250 V - 415 V AC/
250 V - 500 V DC
LC2D09 ...D32
LC2D40A ... D80A
 U 0.85...1.1 Uc BNE EHE KUE USE
LC2 D40A ...D80A
U 0.8...1.2 Uc BBE              

TeSys D Green Contactors

For Load Control from 25 to 80 A Category AC-1

3-Pole Contactors
Non Inductive Loads
Maximum Current (Ɵ ≤ 60 °C) Utilisation Category AC-1
Number
of Poles
Instantaneous
Auxiliary
Contact
Partial reference,
to be completed by adding the control voltage code
Weight
    Fixing  
A           Kg
Connection by Screw Clamp Terminals
25 3 1 1             LC1D09●●●
or        LC1D12●●●
0.368
0.373
32 3 1 1 LC1D18●●● 0.378
40 3 1 1 LC1D25●●● 0.433
50 3 1 1            LC1D32●●●
or       LC1D38●●●
0.438
0.442
Connection by EverLink, BTR Screw Connectors
60 3 1 1 LC1D40A●●● 0.992
80 3 1 1            LC1D50A●●●
or       LC1D65A●●●
0.997
1.002
4-Pole Contactors 
Connection by EverLink, BTR Screw Connectors
60 4 1 1 LC1DT60A●●● 1.230
80 4 1 1 LC1DT80A●●● 1.290
4-Pole Changeover Contactors 
Connection by EverLink, BTR Screw Connectors
60 4 1 1 LC2DT60A●●● 2.460
80 4 1 1 LC2DT80A●●● 2.580
Control Voltage Codes
AC/DC Supply
Volts 24 (DC Only) 24-60 48-130 100-250 250 V - 415 V AC
/ 250 V - 500 V DC
LC1 D09...D65A and LC DT60A...DT80A
U 0.85 .... 1.1 Uc   BNE EHE KUE USE
LC1D40 to LC1D65, LC●DT60A to LC●DT80A
U 0.8...1.2 Uc BBE          

TeSys Contactors

TeSys D Contactors and Reversing Contactors

Instantaneous Auxiliary Contact Blocks

Instantaneous Auxiliary Contact Blocks For Connection By Screw Clamp Terminals
For Use In Normal Operating Environment
Clip-On MountingNumber of 
Contacts per Block
Composition
Reference  
   
Front 1 1 LADN10  
    1 LADN01  
  2 1 1 LADN11  
    2 LADN20  
    2 LADN02  
  4 2 2 LADN22 LADN22S
    1 3 LADN13  
    4 LADN40  
    4 LADN04  
    3 1 LADN31  
  4 Incl. 1 N/O & 1 N/C Make Before Break 2 2 LADC22  
Side 2 1 1 LAD8N11  
    2 LAD8N20  
    2 LAD8N02  
For Terminal Referencing Conforming To EN 50012
Front on 3P Contactors & 2 1 1 LADN11G  
4P Contactors 20 to 80 4 2 2 LADN22G  
With Dust and Damp Protected Contacts, For Use In Particularly Harsh Industrial Environments
Front 2 2 LA1DX20  
    1 1 LA1DX11  
    2 LA1DX02  
    2 2 LA1DY20  
  4 2 2 LA1DZ40  
    2 1 1 LA1DZ31  
Maximum Number Of Auxiliary Contacts Per Rating
Contactors Instantaneous Auxiliary Contact Time delay
Coil Pole Rating ref. Side Mounted   Front Mounted Front Mounted
1 Contact 2 Contact 4 Contact
AC/DC Compatible 3P LC1 D09...D38 1 on Right Hand Side and- - 1 or 1 or 1
  LC1 D40A...D80A 1 on RH or LH Side and- - 1 or 1 or 1
4P LC1 DT60A and DT80A 1 on RH or LH Side and- - 1 or 1 or 1

TeSys Contactors

TeSys D Contactors and Reversing Contactors

Time Delay Auxiliary Contact Blocks, Mechanical Latch Blocks

Time Delay Auxiliary Contact Blocks For Connection By Screw Clamp Terminals
Clip-On
Mounting
Number
of Contacts
Time delayReference
TypeSetting Range
Front 1 N/O+1 N/C On-Delay 0.1...3 s LADT0
      0.1...30 s LADT2
      10...180 s LADT4
      1...30 s LADS2
    Off-Delay 0.1...3 s LADR0
      0.1...30 s LADR2
      10...180 s LADR4


Mechanical Latch Blocks
Clip-on
Mounting
Unlatching
Control
For Use on ContactorPartial reference to
be completed with
coil voltage code
PoleCoil (3)Reference
Front Manual
or
Electric
3 AC or DC or AC/DC LC1D09 ... D38 LAD6K10
    LC1D40A ... D80A
4 AC or DC or AC/DC  LC1DT20... DT40
    LC1DT60A... DT80A


Coil Voltage Codes
Volts 50/60 Hz 24 32/36 42/48 60/72 100 110/127 220/240 256/277 380/415
Code B C E EN K F M U Q

TeSys Contactors

TeSys D Contactors and Reversing Contactors Accessories

Electronic Serial Timer Modules
To be mounted on 3P contactors LC1D40A to D80A using LAD4BB3 wiring adapter (to be ordered separatly)
On-Delay Type
Operational voltage ~Time delayReference
24...250 V
LC1D40A ... LC1D80A 0.1...2  LA4DT0U
1.5...30 s LA4DT2U
25...500 s LA4DT4U

TeSys Contactors

TeSys D Contactors and Reversing Contactors Accessories

Power Connection Accessories
Terminal Block For Supply to One or More GV2 G Busbar Set GV1G09
Set of 63 A Busbars
for Parallelling of Contactors
2 Contactors LC1 D09...D18 or D25...D38 GV2G245
4 Contactors LC1 D09...D18 or D25...D3 GV2G445
Set of 115 A Busbars
for Parallelling of Contactors
2 Contactors LC1 D40A...D80A GV3G264
3 Contactors LC1 D40A...D80 GV3G364
Set of S-Shape Busbars For circuit breakers GV3 P●● and GV3 L●●
and contactors LC1 D40A...D6
GV3S


Mounting Accessories
Retrofit plate for screw
fixing
For replacement of LC1 D40 to D65 by LC1 D40A to D80A 1 LAD7X3
Size 4 Allen key, insulated,
1000 V
For use on contactors 
LC1 D40A to LC1 D150
5 LADALLEN4

TeSys Contactors

Component Parts For Assembling Reversing Or Changeover Contactors Pairs

For 3-Pole Reversing Contactors For Motor Control
Contactors with Screw Clamp Terminals or Connectors. Horizontally Mounted, Assembled by Customer.
DescriptionFor Contactors
(2 Identical Contactors)
Reference
Kits for Assembly of Reversing Contactors
Kit Comprising: LC1 D09 to D38 LAD9R1V
A mechanical interlock LAD 9V2
   with electrical interlocking
LAD 9V
A set of power connections LAD 9V5
   (parallel) and
LAD 9V6 (reversing).
Kit Comprising: LC1 D09 to D38 LAD9R1 
A mechanical interlock LAD 9V2
   without electrical interlocking
A set of power connections LAD 9V5
   (parallel) and
LAD 9V6 (reversing).
Kit Comprising: LC1 D40A to D80A LAD9R3
A mechanical interlock LAD 4CM
A set of power connections LA9 D65A6
Mechanical Interlocks
Mechanical interlock without integral
electrical interlocking
LC1 D09 to D38 LAD9V2
LC1 D40A to D80A LAD4CM